维修包米勒伺服驱动器:705:Motor temperature for characteristic curve of ASM slip invalid, lower than -50°C or higher than 200°C。ASM滑动特性曲线的电机温度无效,低于-50°C或高于200°C
宜兴鲍米勒伺服驱动器维修技巧:The motor temperature that is measured via the KTY encoder is monitored for asynchronous motors due to slip characteristic curves
If the temperature is lower than -50°C or higher than 200°C, the temperature values are assumed to be invalid and the error will be triggered.通过KTY编码器测量的电机温度因滑动特性曲线而对异步电机进行监测如果温度低于-50°C或高于200°C,则假定温度值无效,并将触发错误。
Cause:
The KTY motor temperature encoder was incorrectly connected or not at all connected. KTY电机温度编码器连接不正确或根本没有连接。
Remedy through: 补救措施:Check connections and cable of KTY motor temperature encoder.检查KTY电机温度的连接和电缆编码器。
Monitoring may be deactivated for intended operation without temperature encoder.在没有温度编码器的情况下,可针对预期操作停用监控。
Cause: 原因:
KTY motor temperature encoder defective. KTY电机温度编码器故障。
Remedy through: A defective KTY motor temperature encoder generally requires
motor replacement.有缺陷的KTY电机温度编码器通常需要电机更换。
Monitoring may be deactivated for intended operation without temperature encoder.
在没有温度编码器的情况下,可针对预期操作停用监控。
Cause:原因:
Evaluation switch of the KTY motor temperature encoder in the drive controller is defective. 驱动控制器中KTY电机温度编码器的评估开关存在故障。
Remedy through: Drive controller replacement.更换驱动器控制器。
Monitoring may be deactivated for intended operation without temperature encoder.
在没有温度编码器的情况下,可针对预期操作停用监控。
维修包米勒伺服驱动器 BUM62T-100-130--M-024 *维修BUM60, BUM61, BUM62, BUM63, BUM, BKH63, BUS621, BUS622, BUS623, BUS624, BUG622, BUG623, BUM616, BUM617, BUM618, BUM619, BUG3, BUG2, BUG20, BUS3, BUS2, BUS20, BUS6V, BMAXX 4400, BMAXX 4500
转载请注明出处:上海仰光电子科技专业伺服驱动器维修,伺服电机维修
本文链接:http://www.shygdz.com/fuwu/Services_Show21195.htm
伺服驱动器维修 伺服电机维修 触摸屏维修 变频器维修
电话:021-50157782
手机:13817011982 微信同号
邮箱:shygdzi@163.com
联系人:张工
网址:http://www.shygdz.com
【 我们确保修好测试好给客户!!!!】
下一篇:东曹凝胶渗透色谱仪HLC-8321GPC常见故障维修方法